FAQ about INVT BPD Series Solar Pump Inverter

Some questions about INVT BPD series solar pump inverter

Q1: Keypad display AL-S, and system stop running?

A: AL-S is weak light alarm, means the current sunshine is not enough to drive the pump, result in the running frequency Hz is less than lower limit: (lower limit: P15.05*P00.03)

Conditions of AL-S:

a. Running frequency is less than P15.05*P00.35, and keep more than P15.20 time.

b. Current PV output voltage(P18.01) is less than undervoltage point.

(1HP: 60V, 2HP/3HP: 80V)

If current condition meets a or b, BPD will display AL-S alarm.

If P15.29=0, the system will switch to AC power input channel.

Q2:Single phase pump cannot start?

A. If removed the capacitors? Please remove the capacitors as the following photo, and make sure the resistor value U&V is the biggest OHM, U&W is the smallest value.

After the capacitors are removed, need to set P04.34=01. ( when set this value, Press SHIFT key can change the setting bit.)

If you want to know more,you can click on it and visit our website.