Q1: Keypad display AL-S, and system stop running?
A: AL-S is weak light alarm, means the current sunshine is not enough to drive the pump, result in the running frequency Hz is less than lower limit: (lower limit: P15.05*P00.03)
Conditions of AL-S:
a. Running frequency is less than P15.05*P00.35, and keep more than P15.20 time.
b. Current PV output voltage(P18.01) is less than undervoltage point.
(1HP: 60V, 2HP/3HP: 80V)
If current condition meets a or b, BPD will display AL-S alarm.
If P15.29=0, the system will switch to AC power input channel.
Q2:Single phase pump cannot start?
A. If removed the capacitors? Please remove the capacitors as the following photo, and make sure the resistor value U&V is the biggest OHM, U&W is the smallest value.
After the capacitors are removed, need to set P04.34=01. ( when set this value, Press SHIFT key can change the setting bit.)