WECON PLC Extend board LX3V-2PT2DA-BD
Make sure to power off the PLC before mounting the 2AD2DA module.and remove the top cover of PLC, screwed to the PLC.
Caution: when output current, make sure that the load resistance should be less than 500Ω, otherwise the output will be lower.
Warring: make sure to power off the PLC before mounting or removing the BD module.and put the cover in right place.
2. Terminal Instruction
①IN - 2PT:
Sensor type: 2 or 3 wires PT100
L1+:First channel PT100 signal input (+)
L1-:First channel PT100 signal input (-)
L2+:Second channel PT100 signal input (+)
L2-:Second channel PT100 signal input (-)
VI-:Common
②PT Wire Instruction:
2 Wires PT100:Connect L1- with VI- by,connect L1+ to PT100+, connect L1- to PT100-, same for second channel.
3 Wires PT100:Use two wires (two of three wires with same color on PT100) connect to L1- and VI-, connect another wire to L1+.
③OUT - 2DA:
Output current range:4~20mA
I1+:First channel current output (+)
I1-:First channel current output (-)
I2+:Second channel current output (+)
I2-:First channel current output (-)
3. Address instruction
Address Description
M8112——Ch1 sensor flag OFF:PT100 connected
M8113——Ch2 sensor flag OFF:PT100 connected
M8114——Ch3 output flag OFF:current mode (4~20mA: 0~2000)
M8115——Ch4 output flag OFF:current mode (4~20mA: 0~2000)
D8112——Ch1 temperature (Unit:0.1 degree centigrade)
D8113——Ch2 temperature (Unit:0.1 degree centigrade)
D8114——Ch3 digital value
D8115——Ch4 digital value