WECON PLC Extend board LX3V-2PT2DA-BD

Make sure to power off the PLC before mounting the 2AD2DA module.and remove the top cover of PLC, screwed to the PLC.

Caution: when output current, make sure that the load resistance should be less than 500Ω, otherwise the output will be lower.

Warring: make sure to power off the PLC before mounting or removing the BD module.and put the cover in right place.

2. Terminal Instruction

①IN - 2PT:

Sensor type: 2 or 3 wires PT100

L1+:First channel PT100 signal input (+)

L1-:First channel PT100 signal input (-)

L2+:Second channel PT100 signal input (+)

L2-:Second channel PT100 signal input (-)

VI-:Common

②PT Wire Instruction:

2 Wires PT100:Connect L1- with VI- by,connect L1+ to PT100+, connect L1- to PT100-, same for second channel.

3 Wires PT100:Use two wires (two of three wires with same color on PT100) connect to L1- and VI-, connect another wire to L1+.

③OUT - 2DA:

Output current range:4~20mA

I1+:First channel current output (+)

I1-:First channel current output (-)

I2+:Second channel current output (+)

I2-:First channel current output (-)

3. Address instruction

Address Description

M8112——Ch1 sensor flag OFF:PT100 connected

M8113——Ch2 sensor flag OFF:PT100 connected

M8114——Ch3 output flag OFF:current mode (4~20mA: 0~2000)

M8115——Ch4 output flag OFF:current mode (4~20mA: 0~2000)

D8112——Ch1 temperature (Unit:0.1 degree centigrade)

D8113——Ch2 temperature (Unit:0.1 degree centigrade)

D8114——Ch3 digital value

D8115——Ch4 digital value